產(chǎn)品詳情
SIMATIC S7-300, Analog b SM 331, Isolated 8 AI, resolution 13 bits
U/I/resistor/Pt100, NI100, NI1000, LG-NI1000, PTC/KTY, 66 ms conversion time;
1x 40-pole
Input current
from backplane bus 5 V DC, max. 90 mA
Power loss
Power loss, typ. 0.4 W
Analog bs
Number of analog bs 8
● For resistance measurement 8
permissible b voltage for voltage b (destruction limit),
max.
30 V; 12 V continuous, 30 V for max. 1 s
permissible b current for current b (destruction limit),
max.
40 mA
Input ranges
● Voltage Yes
● Current Yes
● Thermocouple No
● Resistance thermometer Yes
● Resistance Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
— Input resistance (0 to 10 V) 100 k?
● 1 V to 5 V Yes
— Input resistance (1 V to 5 V) 100 k?
● 1 V to 10 V No
● -1 V to +1 V Yes
— Input resistance (-1 V to +1 V) 100 k?
● -10 V to +10 V Yes
— Input resistance (-10 V to +10 V) 100 k?
● -2.5 V to +2.5 V No
● -250 mV to +250 mV No
● -5 V to +5 V Yes
— Input resistance (-5 V to +5 V) 100 k?
● -50 mV to +50 mV Yes
— Input resistance (-50 mV to +50 mV) 100 k?
● -500 mV to +500 mV Yes
— Input resistance (-500 mV to +500 mV) 100 k?
● -80 mV to +80 mV No
Input ranges (rated values), currents
● 0 to 20 mA Yes
— Input resistance (0 to 20 mA) 100 ?
● -10 mA to +10 mA No
6ES73311KF020AB0
Page 1/3 9/13/2024 Subject to change without notice
© Copyright Siemens
● -20 mA to +20 mA Yes
— Input resistance (-20 mA to +20 mA) 100 ?
● -3.2 mA to +3.2 mA No
● 4 mA to 20 mA Yes
— Input resistance (4 mA to 20 mA) 100 ?
Input ranges (rated values), thermocouples
● Type B No
● Type C No
● Type E No
● Type J No
● Type K No
● Type L No
● Type N No
● Type R No
● Type S No
● Type T No
● Type U No
● Type TXK/TXK(L) to GOST No
Input ranges (rated values), resistance thermometer
● Cu 10 No
● Ni 100 Yes; Standard/climate
— Input resistance (Ni 100) 100 M?
● Ni 1000 Yes
— Input resistance (Ni 1000) 100 M?
● LG-Ni 1000 Yes; Standard/climate
— Input resistance (LG-Ni 1000) 100 M?
● Ni 120 No
● Ni 200 No
● Ni 500 No
● Pt 100 Yes; Standard/climate
— Input resistance (Pt 100) 100 M?
● Pt 1000 No
● Pt 200 No
● Pt 500 No
Input ranges (rated values), resistors
● 0 to 150 ohms No
● 0 to 300 ohms No
● 0 to 600 ohms Yes
— Input resistance (0 to 600 ohms) 100 M?
● 0 to 6000 ohms Yes
— Input resistance (0 to 6000 ohms) 100 M?
Thermocouple (TC)
Temperature compensation
— beterizable No
— internal temperature compensation No
— external temperature compensation with
compensations socket
No
Characteristic linearization
● beterizable Yes
— for thermocouples No
— for resistance thermometer yes; Pt100 standard/air con.; Ni100 standard/air con.; Ni1000 standard/air con.;
LG-Ni1000 standard/air con.
Cable length
● shielded, max. 200 m; max. 50 m at 50 mV
Analog value generation for the bs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 13 bit
● Integration time, beterizable Yes; 60 / 50 ms
● Basic conversion time (ms) 66 / 55 ms
● Interference voltage suppression for interference
frequency f1 in Hz
50 / 60 H